9.2
Overview – micro module terminals
Basic module
IQ8 Control
Fig. 82: Overview – micro module terminals
esserbus
®
module
(Part No. 784382 / 784382.10 / 784382.D0)
for max. 127 loop devices, e.g. Fire detectors series
IQ8Quad, 9200 and esserbus
dividable in 127 individual zones
Quiescent
current: approx. 25 mA.
Total current for loop devices max. 40 mA
®
esserbus
PLus module
(Part No. 804382 / 804382.10 / 804382.D0)
or max. 127 loop devices, e.g. Fire detectors
IQ8Quad, series 9200, esserbus
loop compatible alarm devices, dividable in 127
individual zones
Quiescent
current: approx. 25 mA.
Total current for loop devices max. 180 mA
Master box activation module (Part No. 784385)
To connect and control the MFAB operation.
Quiescent
current: approx. 15 mA.
Observe permitted torque (max. 0.4 Nm) of the terminals!
FB 798951.10.GB0 / 04.15
X3
1 2 3 4 5 6 7 8
micro module
®
-transponders,
®
-transponders and
Fire Alarm Control Panel IQ8Control C / M
not used
MFAB reset (+ 12 V oder + 24 V / 300 mA)
PPrimary loop to MFAB (+ MFAB)
unlock fire dept. box (max. 300 mA)
acknowiedgment
1 2
3 4 5
6
7 8
A +
not used
A -
not used
B +
not used
B -
not used
not used!
A
A
B
B
-
+
-
+
1 2
3 4 5
6
7 8
+ MFAB
GND
B -
B +
A -
A +
93