Honeywell ESSER IQ8Control C Installation Instruction page 101

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

Type/extent of the detector replacement
The type and external switching of the exchanged detector are in
conformance. For example, if a defective OHI-detector without a detector
base output is replaced with a new OHI-detector without a detector base
output.
The detector type changes , the external switching remains the same. For
example, an optical smoke detector is replaced with an OHI- detector and
the existing external wiring is not changed.
During the replacement of detectors, the external switching is removed;
the detector type remains unchanged. For example, an OHI-detector with
a relay output is replaced with an OHI-detector without a relay output. The
change in the external switching from relay to LED outputs (or the
converse) is not recognised.
During the replacement of detectors, the external switching is added, the
detector type remains unchanged. For example, an OHI-detector without a
relay output is replaced with an OHI-detector with a relay output. The
change in the external switching from relay to LED outputs (or the
converse) is not recognised.
An isolating circuit is removed, the detector type remains unchanged. For
example, an OHI-detector with an isolating circuit (zone isolator) is
replaced with an OHI-detector without an isolating circuit.
An isolating circuit is inserted, the detector type remains unchanged.
The wiring of the loop is changed. For example, during the replacement of
detectors, a new detector is inserted in an additional spur loop.
Replacement of identical esserbus
transponder Type 12 relay is replaced with an identical esserbus
transponder. The programming of the 12 relay outputs is not changed.
Replacement of dissimilar esserbus
transponder is replaced by another type or the designation / programming
of the outputs is changed.
Replacement of an esserbus
the converse.
Replacement of a manual call point with an esserbus
the converse.
*
Operation without Service-PC available in the installer level of the Fire Alarm Control Panel IQ8Control C/M.
FB 798951.10.GB0 / 04.15
®
transponders. A defective esserbus
®
transponders. An esserbus
®
transponder with an automatic detector and
Fire Alarm Control Panel IQ8Control C / M
®
®
®
®
transponder and
without
displayed
Service-PC *
trouble code
yes
---
St : 081-087/
yes
095
no
St : 088
yes
St : 089
no
St : 088
yes
St : 090
no
St : 066
yes
---
no
St : 080
no
St : 080
no
St : 080
101