Honeywell ESSER IQ8Control C Installation Instruction page 118

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C / M
Trouble
Possible cause
Code No.
Communication between
esserbus
039
FACP  disturbed for 100
seconds.
Monitoring of the esserbus
041
transponder for relay 1 has
identified a fault.
Monitoring of the esserbus
042
transponder for relay 2 has
identified a fault.
Communication between
®
esserbus
transponder 808615 and the
043
8010 fire and extinguishing
panel has been malfunctioned
for over 100 seconds.
Communication between
FACP and esserbus
communication transponder
044
for the 8010 fire and
extinguishing panel has been
malfunctioned.
048
052 / 053
060
Short circuit detected behind
060
the isolator of the esserbus
transponder.
Failure of the internal data
062
communication of the
®
esserbus
Detector data assignment
063
incomplete or EEPROM
failure.
Loop wiring has been
066
changed.
Detector cannot be addressed
with serial number. The
067
detector changed at this
location is faulty or absent.
The detector that was
positioned at this location has
been installed at a different
068
location. One or more
detectors on the loop have
been interchanged.
118
1st. measure
transponder and
Notify Customer Service.
With 10 kOhm terminating
®
resistance:
The degree of resistance
measured is outside of the
monitoring range.
With 10 kOhm terminating
®
resistance:
The degree of resistance
measured is outside of the
monitoring range.
Check correct functioning of
the 8010 fire and
communication
extinguishing panel. Correct
any malfunctions of the fire
and extinguishing panel and
switch on the esserbus
communication transponder
via the FACP keyboard.
®
Notify Customer Service.
see 001
see 020
see 028
®
Switch-on transponder or
loop. If error occurs again
transponders CPU.
refer to 2
Repeat detector data
assignment on the relating
loop.
Connect service PC and
perform wiring recognition.
Check location to see whether
detector is absent or
improperly installed in
detector base. Switch on loop,
perform test on detector zone.
If this change is desired, you
must activate the >Detector
change< function at the
FACP.
2nd. measure
With EOL-O end-of-line:
The set monitoring current does
not correspond to this
measurement value; cable
impedance is too high.
With EOL-O end-of-line:
The set monitoring current does
not correspond to this
measurement value; cable
impedance is too high.
®
-
---
---
---
see 028
Press reset button on the
transponder board, or disconnect
transponders power supply. If
nd
measure.
error occurs again replace
transponder.
If error occurs again replace
transponder
Change detector. Activate
>Detector change< function in
panel.
If this change is not desired,
connect service PC and run a
wiring recognition. Re-program
customer data.
---
Notify Customer Service.
---
---
---
---
see 028
---
FB 798951.10.GB0 / 04.15