9.10 Obstacles preventing setting the system

According to Ways of setting (see Parameters tab), the control panel may check for triggered or fault statuses
of individual devices or a particular section while setting each section of the system. In line with this option, the
control panel indicates some obstacles during setting (passable obstacles) and some of the statuses and may
even prevent the system from setting when they occur (impassable obstacles).
One of the most common obstacles is any system fault (indicated by a yellow system indicator), a loss of
connection with a wireless detector or a triggered status detector (typically a magnetic opening sensor) set with
a delayed zone reaction (front door and garage door sensors), low system battery, a long lasting power supply
failure or a communication fault of one of the communicators. It is influenced by the system profile.
An impassable obstacle preventing setting the system is for example a triggered status detector (usually
a magnetic door opening sensor) set up to an Instant reaction. Devices which belong in this group are window
opening, balcony or backdoor detectors but it can also be critical systems faults such as fault of backup power
supply or fault of communication to the ARC. The reasons which prevent system settings are different according
to the pre-set system profile. An exception in preventing the system from setting a section which doesn't check
for any triggered detectors or faults is the automatic setting by a calendar using the option "Set ... Always".
The calendar will always set each section provided it's configured to perform such an action.
Pulse detector triggering (e.g. motion detectors) cannot prevent setting.
System informs you about setting with an active zone by SMS report (to group of users with predefined alarm
reports) with a detailed description.
Ways of setting - table overview
System keypad
Will set always despite faults
Set always
or triggered devices status
While attempting to set with a
fault or a triggered device, the
keypad flashes for 8 s after
Set with
which the system will
warning
automatically set. It's possible
to set the system by pressing
the functional button again or
by pressing the Enter key.
While attempting to set with a
fault or a triggered device, the
keypad flashes for 8 s after
Set after
which the system will
confirmation
automatically set. It's possible
to set the system by pressing
the functional button again or
by pressing the Enter key.
While attempting to set with a
fault or a triggered device, the
Will not set
keypad flashes for 8 s after
with an
which the system will
active
automatically set. It's possible
element
to set the system by pressing
the functional button again or
by pressing the Enter key.

9.11 Unsuccessful setting

It is a security function thanks to which the control panel checks within the exit delay if setting the system
can be executed and the security of the protected premises is not limited by the following cases. If the function
is enabled, then unsuccessful setting can be caused by:
1. Instant detector activation anytime during the exit delay (someone enters to an already protected area)
2. Permanent activation of a detector with a delay reaction after the exit time has already expired (The user
forgot to close the main door, garage or gate, etc..)
JA-14K(R) Security System Control Panel
Via voice
menu/SMS/remote
controller/calendar
Will set always
Will set always
despite faults or
despite faults or
triggered devices
triggered devices
status
Will set always
Will set always
despite faults or
despite faults or
triggered devices
triggered devices
status
Will set always
Will set always
despite faults or
despite faults or
triggered devices
triggered devices
status
Will not set when a
Will always set
triggered detector is
despite faults or a
set to an INSTANT
triggered devices
zone reaction
37 / 72
N-Link
Web and smart app
Will set always despite
faults or triggered devices
status
status
Will set according to
"Ways of setting" in the
Service configuration tab
status
Will set according to
"Ways of setting" (with Set
with check / set with no
check) in the Service
status
configuration tab
Will not set when a
triggered detector is set to
an INSTANT zone
status
reaction
MNX22101