8.7 Fault caused by loss of a device

Every device in the system is supervised by the control panel. BUS devices are supervised allways, wireless
devices regarding the Parameters tab / Supervision of wireless device checkbox. When the communication with
the device is lost (no response within a pre-set time) then the system triggers the event "Fault activation". The
communication time-out is a fixed time and cannot be changed. For BUS devices it is 8 s and for wireless
120 min from the last communication.
Optionally Fault can be triggered when the radio module detects RF jamming or some kind of RF interference
which takes a minimum 30 s at 2 detection levels.

9 System control options

The security system can be controlled a few ways. Basic control options are local or remote. Other options are
mentioned by the following table:
Type
Way/mode
Keypad
(authorization and
functional button)
RFID reader
(authorization only)
Local
Calendar
N-Link software
Voice menu
Remote controller
SMS message
Remote
Dialling in from
authorized
telephone number
N-Link software
All mentioned ways can be used for system control (setting, partial setting, unsetting) for PG output control (ON,
OFF, timing).

9.1 Way of authorization

Authorization is the key factor to control the system and to verify if the user is really authorized for operation.
According to the authorization procedure the system decides if the user is authorized to set or unset sections,
switch on or off PG outputs using functional buttons or if he can only browse the system status and history log
using a keypad menu. Every user can have the following options assigned to authorize himself:
− Access code (4 or 6-digit number)
− RFID tag (selection from one variant)
− Telephone number for authorization during remote access by telephone call or by SMS (when a
supplementary GSM dialler is connected)
JA-14K(R) Security System Control Panel
Device
JA-10E, JA-15E
radio module for
wireless keypad
JA-10E, JA-15E
radio module for
wireless keypad
10 calendar actions
PC with Windows
Supplementary
Telephone
GSM or PSTN
JA-16J
Supplementary
Cell phone
Supplementary
Telephone (PG
GSM or PSTN
control only)
Supplementary
PC with Windows
(XP SP 3 or higher)
30 / 72
Condition
Operation can be performed after
The JA-111R
user authorization and pressing
a specific functional button or also
The JA-111R
Operation can be performed after
user authorization or using an RFID
Every calendar action has options
to select: event, time of its
performance, day of the week.
It can control sections and PG
outputs. PG outputs can be blocked.
Sections can be controlled and also
USB cable
PG outputs after authorization.
Calling the system telephone
number and control system by DTMF
dialler
tones after authorization.
The JA-111R
Setting and unsetting by pressing
radio module
a pre-set button of a remote.
Authorized command for setting
or unsetting sections and also
GSM dialler
For every authorized telephone
number one specific PG output
dialler
Sections and PG outputs
GSM or LAN
can be controlled by virtual keypad
dialler
Control description
via the keypad menu.
tag or entering a code
control of PG outputs.
can be controlled.
after authorization.