4 Before system installation

Select a hidden place for the control panel (inside the protected area) where mains supply
is available.
The mains supply of the control panel may only be installed by a person with the required
electrical qualifications.
The manufacturer doesn´t allow people to power the control panel up from other alternate
power supply sources such as high capacity batteries charged by solar energy and so on.
The control unit JA-14K(R) provides power supply terminals to select from 2 type of power
supply voltage networks: ~230 V / 50 Hz and ~110 V / 60 Hz. According to the type of
power supply voltage system, the correct connection terminal and the corresponding fuse
must be used in comply with chapter no. 16 Technical specifications.
The power supply of the control panel has double safety separation of the circuits.
No protective conductor is connected.
During the installation and connection of the BUS components of the control panel all the
power supply of the control panel must be completely off.
The manufacturer declines any liability for damage if the system is installed or set
improperly.
1. The arrangement and configuration of the system has to correspond to the design documentation of an
alarm system according to the technical specification CLC/TS 50131-7, consultation with a customer and the
valid technical norms for electrical installations.
2. Prepare the power supply of the control panel – use a suitable cable with double insulation and
a cross-section of 0.75 to 1.5 mm². Voltage surge protection on the control panel mains supply
is recommended. It is also recommended to use a single cable with a circuit breaker (2 A-6 A) and it also
functions as a main switch.
Caution: Don´t connect any other electrical appliance to this specific circuit, not even power for external PG
outputs or a heating system or any other device related to control panel functions (heat control etc.).
Put a sticky label marked "Don´t switch off" on the circuit breaker placed on the switchboard.
3. Put some overvoltage protection in the mains circuit for the control panel.
4. Attach the control panel straight onto the wall or any other incombustible surface. Ensure there are no metal
objects which could negatively influence transmitting or receiving radio signals (radio module and GSM
communicator). Use the supplied template to prepare holes for fasteners. Put the screws through the upper
holes in the plastic housing to keep it 1 cm from the wall, then hang the control panel housing on it. Also put
an additional screw through the lower hole(s) and screw it in as well to stabilize the position of the control
panel. Tighten all the screws.
5. Optional using of power cord does not meet the certification requirements.

5 Installation of BUS devices

The BUS of the JA-10 is meant to be used with a BUS devices of the JA-10 system. Proceed with the following
procedure:
1. During the connection of any BUS modules the power supply of the control panel must be completely off
(backup battery as well).
2. Follow the installation manuals of individual devices.
3. The BUS cable must be installed inside the area that is protected by the system. Inside the walls, metal
pipes, in a lower ceiling or through places which cannot be easily accessed.
4. During the connection of BUS devices pay attention to the colour of wires (red, yellow, green, black).
Connection of third party devices or a device of a different producer is possible via an appropriate module such
as the JA-116H or JA-114HN. The producer cannot guarantee proper functioning of the connected device even
not its security grade.