Hard-Wired Zone Input Setting; Exit / Entrance Delay; Alarm Duration; Pgx And Pgy Output Functions - jablotron MAESTRO JA-65 Installation Manual

Hide thumbs Also See for MAESTRO JA-65:
Table of Contents

Advertisement

12.2. Hard-wired zone input setting

If there is a 65H module in the control panel, wire operated detectors can be connected to the control panel. Setting of the
zone inputs is possible by entering:
60 nn xys
where: nn = zone number: 01 to 16
x = input triggering: 0 = off, 1 = Normally Closed, 2 = balanced loop (EOL resistor 10 kΩ), 3 = double
balanced loop (EOL resistors 2x10 kΩ)
y = reaction: 0 = Instant, 1 = Delayed, 2 = Fire, 3 = Panic, 4 = Tamper, 5 = Next delayed, 6 = control
s = address to section, 1 = A, 2 = B, 3 = C (shared common section, which is armed only if both A and B
sections are armed). If the control panel is not split, select s=1; if you select s=2 then this zone will be
automatically bypassed within partial arming. For details about splitting see section 12.22.
Notes:
• If you will not use a particular input, switch it off with x = 0
• Next delayed input (y=5) provides entrance delay only if in the moment of its triggering the entrance delay has been in progress
(activated before by any delayed input). If no delayed input is triggered before next delayed, the triggering will cause instant alarm.
• Addressing of inputs to section C when the control panel is not split has the same effect as addressing to B section (i.e. automatic
bypass while partial arming is used).
• If y=6 is programmed, then each triggering of this input changes arming status (arm – disarm – arm...) of the entire system or just
the corresponding section if the system is split.
Example: to set zone 2 input as a balanced loop with an instant reaction, addressed to A section, enter: 60 02 201
Factory default setting: all hard-wired inputs are switched off.

12.3. Exit / Entrance delay

To change the duration of the exit and entrance delay (both of them) enter 21x (where x represents time in seconds x10).
The delay can be selected from 10 to 90 seconds.
Example: to select an Exit and Entrance delay duration of 20 seconds, enter 212
Factory default setting: 30 seconds

12.4. Alarm duration

The alarm duration can be selected from 1 to 8 minutes (or 10 seconds or 15 minutes) entering 22x (where x represents
time in minutes, for x=0 the duration will be 10 seconds, for x=9 the duration will be 15 minutes).
Example: to select an alarm duration of 5 minutes, enter 225
Factory default setting: 4 minutes

12.5. PgX and PgY output functions

The control panel outputs PgX and PgY can have different functions, depending on parameter x in the corresponding
sequence:
2 3 x – determines triggering of PgX
2 4 x – determines triggering of PgY
where x represents the following functions (non split system):
0 Chime – triggered during the entrance delay (pre-alarm output)
1 Fire – triggered by a fire alarm (by a smoke or a gas detector)
2 Arm – activated when the control panel is armed (complete & partial arming)
3 Panic – activated when a silent panic alarm is triggered
4 Alarm – triggered by any audible alarm (except panic alarm)
5 Door – activated for 5sec. after
6 Home – activated when the control panel is partially armed (Home arming)
7 No AC – triggered by an AC power failure
8 Phone/F8 – output can be operated remotely by phone or by SMS (if this feature is supported by installed
communicator) or locally from the keypad by F81 (ON) and F80 (OFF). If a code is requested to operate the system
then the F8x instruction should be followed by a valid user code.
Example: the PgX will work as a Panic output when 233 is entered, PgY as Door output when 245 is entered.
Factory default setting: PgX=Chime, PgY=Arm
Note: the control panel also wirelessly transmits the PgX and PgY signals. Wireless output modules UC-216 and UC-222 can be used
to receive the signals (see 25.1.). The function of the UC module output relays is determined by the 23x and 24x setting.
Alarm system JA-65 MAESTRO
(F3) entering (electric door lock opening)
- 11 -
sequence: 60 nn xys
sequence: 2 1 x
sequence: 2 2 x
sequences: 2 3 x & 2 4 x
If the system is split:
x
23x (PgX) 24x (PgY)
0
Alarm A
Alarm A
1
Alarm B
Alarm B
2
Chime A
Chime A
3
Chime B
Chime B
4
Arm A
Arm B
5
Door A
Door B
6
Panic A
Panic B
7
FIRE
NoAC
8
Phone
Phone
MFM51210

Advertisement

Table of Contents
loading

Table of Contents