UPS5000-A-(60 kVA-120 kVA)-H
User Manual
8.6 Bypass Input Electrical Specifications
8.7 Battery Specifications
Issue 05 (2020-01-10)
Item
Input frequency
Input PF
THDi
Item
Input system
Rated input voltage
Rated frequency
Frequency range
Input mode
Item
Battery voltage
Battery management
One-button cold-start
Battery string sharing
Charging voltage
Copyright © Huawei Technologies Co., Ltd.
60 kVA
40-70 Hz
> 0.99 at full load; > 0.98 at half load
THDi < 3% (single mains, linear load)
THDi < 5% (single mains, non-linear load)
60 kVA
Three-phase, four-wire, and PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
50 Hz/60 Hz
± 6 Hz (adjustable, 0.5–6 Hz, ± 2 Hz by default)
The mains input and bypass input use different power
sources or share a power source.
60 kVA
360–528 V DC (12 V batteries, 30–44 batteries, 40 by default)
40–44 batteries: The output power is not derated.
36–38 batteries: The output power in battery mode is
derated to 0.9.
32–34 batteries: The output power in battery mode is
derated to 0.8.
30 batteries: The output power in battery mode is derated
to 0.75.
Intelligent battery management
In the case of mains outage, batteries start the UPS, which
supplies power to loads.
Battery string sharing is supported in a parallel system. No
battery is shared by default.
Equalized charging voltage:
2.3–2.4 V/cell. The default voltage is 2.35 V/cell (30–42
8 Technical Specifications
120 kVA
120 kVA
120 kVA
157