Bypass Input Electrical Specifications; Output Electrical Specifications - Huawei UPS5000-A-400K-SL User Manual

40 kva power modules
Table of Contents

Advertisement

UPS5000-A-(400 kVA-500 kVA)
User Manual (40 kVA Power Modules)

8.5 Bypass Input Electrical Specifications

8.6 Bypass Input Electrical Specifications

8.7 Output Electrical Specifications

Issue 06 (2020-01-10)
Bypass Input
Specifications
Input format
Rated input voltage
Rated frequency
Frequency range
Input mode
Bypass current
sharing
Item
Battery voltage
Battery management
One-button cold-
start
Battery string
sharing
Charge voltage
In monitoring and power versions earlier than V100R001C10SPC008, the battery voltage is 360–480 V
DC (30 to 40 batteries, 32 by default).
Item
Output system
Voltage
Copyright © Huawei Technologies Co., Ltd.
400 kVA
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
50 Hz or 60 Hz
± 6 Hz (0.5–6 Hz, ± 2 Hz by default)
The main and bypass inputs are supplied by one or two power
sources.
In a parallel system, control the cable length to equalize the current.
The current unbalance must be less than 25%.
400 kVA
360–552 V DC (30–46 batteries, 32 by default. The UPS5000-A
power is derated by 6% when 30 batteries are configured.)
Intelligent battery management
In the case of mains outage, batteries start the UPS5000-A, which
supplies power to loads.
Battery string sharing is supported in a parallel system. No battery
string is shared by default.
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
400 kVA
Three-phase, four-wire, and PE wire
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
8 Technical Specifications
500 kVA
500 kVA
500 kVA
182