UPS5000-A-(60 kVA-120 kVA)-H
User Manual
IP address allocation
You can set Allocation to Manual or Automatic. If the UPS is restarted, Allocation automatically
changes to Manual. The IP address is bound as the IP address set last time, allowing you to log in for
the second time.
Item
IP address
Subn. mask
Gateway
Figure 4-10 RS485 communication settings
Item
Comm. address
Baud rate
Parity mode
Issue 05 (2020-01-10)
Manual: After the MDU connects to the PC over a network cable, check that their IP
addresses are two different values on the same network segment.
Automatic: The MDU automatically queries available IP addresses in the connected
network. Ensure that the MDU and PC are on the same network segment.
Description
Specifies the IP address for the
Ethernet.
NOTICE
Ensure that the UPS IP address is
unique on the network segment.
Otherwise, the WebUI display
function may not function properly.
Specifies the subnet mask of the
Ethernet.
Specifies the Ethernet gateway.
Description
This serial port address is
allocated by the user.
Select a baud rate to match the
user's network management
conditions onsite.
Verify the validity of RS485
communication characters. When
a device node adopts RS485
communication, ensure that the
parity modes for the device nodes
are set to the same mode.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
192.168.0.10
1.0.0.0–
223.255.255.255
255.255.255.0
0.0.0.0–
255.255.255.255
192.168.0.1
1.0.0.0–
223.255.255.255
Default Value
Value Range
1
1–254
9600
9600, 19200,
115200
None
None, Odd,
Even
89