Safety Regulations And Emc; Mains Input Electrical Specifications - Huawei UPS5000-A User Manual

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual

8.4 Safety Regulations and EMC

8.5 Mains Input Electrical Specifications

Issue 05 (2020-01-10)
Item
Item
Safety regulations
EMC
Item
Input system
Rated input voltage
Input voltage
Rated frequency
Copyright © Huawei Technologies Co., Ltd.
60 kVA
The UPS power is derated as described in IEC62040-3 when
the altitude is from 1000 m to 4000 m. The upper limit of the
altitude is 4000 m.
60 kVA
EN62040-1: 2013
IEC62040-1: 2013
YD/T2165-2010
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
60 kVA
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
80-280 V AC
If the temperature is 30–40° C, the UPS power is not
derated when the voltage is within 198–280 V AC; the
load is derated to 35% when the voltage is within
198–80 V AC.
If the temperature is 0–30° C, the UPS power is not
derated when the voltage is within 187–280 V AC; the
load is derated to 35% when the voltage is within
187–80 V AC.
50 Hz/60 Hz
8 Technical Specifications
120 kVA
120 kVA
120 kVA
156