UPS5000-A-(60 kVA-120 kVA)-H
User Manual
To prevent short circuits, refer to
DT terminals.
When connecting power cables, comply with the tightening torque listed in
ensure secure connections and prevent safety risks.
Table 3-4 Power cable DT terminal requirements
Model
60 kVA
120 kVA
60 kVA/120
kVA
Issue 05 (2020-01-10)
The battery cable specifications are selected based on 40 batteries by default and
compatible with application scenarios with 30–44 batteries.
Port
Description
Mains input
Bypass input
Battery input
Output
Mains input
Bypass input
(2L1, 2L2,
2L3)
Bypass input
(N)
Battery input
Output
PE
Copyright © Huawei Technologies Co., Ltd.
Table 3-4
and
Table 3-5
Bolt
Specifications
M8 x 30
M8 x 30
M10 x 30
M8 x 30
M10 x 30
M8 x 20
M10 x 30
M12 x 45
M10 x 30
M8 x 20
for the specifications when selecting
Table 3-4
Bolt Hole
Torque
Diameter
203N•m
9 mm
20N•m
9 mm
35N•m
11 mm
20N•m
9 mm
35N•m
11 mm
20N•m
9mm
35N•m
11 mm
55N•m
13 mm
35N•m
11 mm
9 mm
13 N· m
3 Installation
to