Huawei UPS5000-A User Manual page 120

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Item
EOD restart
delay (min)
Undertemp.
alarm thresh.
(° C)
Overtemp.
alarm thresh.
(° C)
Single batt.
float chg.
voltage
deviation alarm
thres. (%)
Single batt. dis.
voltage
deviation alarm
thres. (%)
Batt. charging
capacity
mismatch
Bat mode shut
Backup time
warning
Remain. cap.
warning
Issue 05 (2020-01-10)
Description
restart function for the UPS.
If EOD restart is set to Enable,
the UPS starts working after the
time set for EOD restart delay
when the input recovers from the
power failure upon EOD.
Battery temperatures can be
monitored in a timely manner. If
a battery overtemperature alarm
is detected, the charging current
limit decreases to 0.03 CA.
Battery charging stops if a
battery overtemperature
protection alarm (when the
temperature reaches the high
temperature threshold plus 3° C)
is generated.
Single batt. float chg. voltage
deviation alarm thres. (%) and
Single batt. dis. voltage
deviation alarm thres. (%) are
used to check whether the cells in
each battery string have the same
charge voltage and discharge
voltage. When a value exceeds
the specified range, an alarm is
generated.
The calculation formula is
(Charge/Discharge voltage –
Average voltage)/Average
voltage x 100%.
After this function is enabled, an
alarm is generated if the
configured battery capacity
exceeds the charging capacity of
the rack.
In battery mode, the UPS can
automatically power off
according to the preset shutdown
delay time. If the parameter is
disabled, this function is not
available.
An alarm is generated if this
parameter is set to Enable and
the backup time is less than the
warning threshold.
An alarm is generated if this
parameter is set to Enable and
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
10
1–1440
–5° C
–20° C to +5° C
50° C
35° C to 55° C
10
5–30
20
10–30
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
112