Huawei UPS5000-A User Manual page 179

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
redundant
racks
0096-1
ECO volt.
Abnormal
0098-1
Bypass current
not shared
0150-1
Inverter
asynchronous
0101-1
BSC signal
abnormal
0102-1
Maint. breaker
misoperation
Issue 05 (2020-01-10)
Severity
Cause
excessive.
The configured
number of
redundant racks is
incorrect.
Minor
The ECO bypass
voltage or
frequency is out
of the preset
range.
The ECO bypass
voltage or
frequency range is
incorrectly set.
The bypass input
sequence is
reverse or the
neutral wire is
disconnected.
Minor
The output and
input circuit
breakers are OFF.
The length of the
bypass input or
output cables is
incorrect.
The bypass SCR
open-circuits.
Minor
The bypass
frequency changes
fast.
The output
frequency track
rate is incorrectly
set.
Minor
The dual bus
connector is loose.
Parameters are set
incorrectly.
Critical
The user operation is
incorrect.
Copyright © Huawei Technologies Co., Ltd.
Solution
2. Decrease the configured number of
redundant racks.
1. Check the bypass input voltage
and frequency.
2. Check that the rated voltage, rated
frequency, ECO bypass voltage
range, and frequency range are
correctly set.
3. Check that the bypass cables and
circuit breakers are correctly
connected.
1. Check that the output and bypass
input circuit breakers on each rack
are ON.
2. Check that bypass input and output
power cables on each rack meet
the length requirements.
3. Rectify any bypass SCR open-
circuit.
1. Check that the bypass output
frequency does not change fast.
2. Check that the Output freq. track
rate is properly set.
1. Check the dual bus connector.
2. Check the parameter settings.
1. Shut down the inverter and then
close the maintenance circuit
breaker.
B Alarm List
171