Bypass Input Electrical Specifications - Huawei UPS2000-G Series User Manual

Hide thumbs Also See for UPS2000-G Series:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
Item
Input voltage
Input power
factor (100%
resistive load)
No-load loss
Double-power
input
Startup voltage
Diesel generator
input capacity

9.4 Bypass Input Electrical Specifications

Table 9-6 Bypass input electrical specifications
Item
Bypass voltage
Bypass frequency
tolerance
Bypass overload
capability
Input mode
Issue 21 (2022-10-13)
15 kVA
● 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to
40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
> 0.99
< 200 W
Enabled
120–280 V AC
Minimum 1.5 times the UPS rated capacity
6 kVA
● Upper threshold: 10%, 15%, 20%, 25%, 30%@208 V AC
● Upper threshold: 10%, 15%, 20%, 25%@220 V AC
● Upper threshold: 10%, 15%, 20%@230 V AC
● Upper threshold: 10%, 15%@240 V AC
● Lower threshold: 10%, 20%, 30%, 40%, 50%, 60%
Maximum ±6 Hz (configurable on the LCD)
● Load < 125%: continuous in bypass mode
● 125% ≤ load < 150%: 1 minute in bypass mode
● Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.
One power source
Copyright © Huawei Technologies Co., Ltd.
20 kVA
● 80–280 V AC, single-
phase (When the voltage
is 80–176 V AC, the load
power is linearly derated
to 40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
10 kVA
15 kVA
● One power source
● Two power sources
9 Technical Specifications
20 kVA
125