Huawei UPS5000-A User Manual page 162

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Case
Symptom
The
The buzzer is activated, the
inverter is
Fault indicator is on, the
not
inverter is faulty, and the
normal.
UPS transfers to bypass
mode.
The
The buzzer is activated, the
charger
Fault indicator is on, and the
generate
charging function fails.
an alarm.
The UPS
When the mains is normal,
works in
the UPS works in bypass
bypass
mode and does not transfer to
inverter mode.
mode and
does not
transfer to
inverter
mode.
The
The buzzer is activated, and
bypass is
the Fault indicator is on.
not
normal.
For details about component replacement and maintenance involved in Troubleshooting and Alarm List,
consult Huawei maintenance engineers.
Issue 05 (2020-01-10)
Possible Cause
PFC soft-startup fails.
The power unit is faulty.
The load is overloaded or
short-circuited.
Inverter overtemperature
occurs.
The power unit is faulty.
The charger fails.
The charger experiences
overcurrent.
The charger experiences
undervoltage.
Set the UPS working mode to
ECO mode.
The bypass transfer times
reach the upper threshold.
The bypass thyristor is
damaged.
The bypass unit experiences
overtemperature.
Copyright © Huawei Technologies Co., Ltd.
7 Troubleshooting
Measure
Replace the power unit.
Reduce load or rectify short
circuits.
Install more air conditioners
or ventilation devices to
ensure normal temperatures
inside the equipment room.
Replace the power unit.
Replace the power unit.
Check whether the configured
number of batteries is correct.
If the value is correct but the
alarm persists, replace the
power unit.
Set the working mode
correctly.
Clear the bypass transfer
times on the LCD.
Replace the bypass unit.
Reduce the load, or improve
ventilation.
154

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-a-60kttlUps5000-a-120kttl

Table of Contents