Huawei UPS5000-A User Manual page 101

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Figure 4-15 Input Settings screen
Output Settings
Figure 4-16 Output Settings Screen
Issue 05 (2020-01-10)
Item
Description
Inp. adaptabil.
Input adaptability mode 1: It is
applicable to the normal power
grid and DGs, and DGs that are
sensitive to the output reactive
component. Input adaptability
mode 2: It is applicable to the
normal power grid and DGs, and
input power sources with high
internal resistance.
Item
Description
Outp volt lev.
Specifies the system output
voltage level. This parameter is
configurable only after the
inverter shuts down. After you
change the voltage level, the
upper limit of the bypass voltage
restores to the default value. (If
the voltage level is 380 V or 400
V, the default upper limit is
+15%. If the voltage level is 415
V, the default upper limit is
+10%.)
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
Mode 2
Mode 1, Mode 2
Default Value
Value Range
400
380, 400, 415
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-a-60kttlUps5000-a-120kttl

Table of Contents