5.6.4 Test Data Download
Procedure
Step 1 Log in to the WebUI.
Step 2 Choose Query > Logs, select Cap. test logs or Common test logs from the Log drop-down
list box, click Export, and select a path, as shown in
Figure 5-12 Capacity test logs
Figure 5-13 Common test logs
----End
5.7 Transferring to Maintenance Bypass Mode
Procedure
Step 1 Transfer the UPS to bypass mode.
Step 2 Turn on the maintenance bypass switch.
Issue 05 (2020-01-10)
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads over the maintenance
bypass. If the mains is abnormal, the loads may power off.