UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Input Setting
Issue 05 (2020-01-10)
Item
Description
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
RAM
Enable or disable the memory
verification
check function. If this parameter
is set to Enable, the control chip
RAM working status is checked
regularly. If this parameter is set
to Disable, regular check is
disabled.
Collect real-
If this parameter is set to Enable,
time site
one waveform can be stored
waveform
manually.
BCB trips in
If this parameter is set to Enable,
case of EOD
the BCB will trip in case of
EOD.
Item
Description
D.G. mode
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
D.G. power
Set these two parameters to
limiting (kVA)
control the valid input current
and limiting input current, which
D.G. charger
prevents load impact and
power ratio (%)
facilitates better cooperation
between the UPS and the D.G.
Input cur.
Specifies whether to enable or
limiting
disable input current limiting to
protect generators.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
Disable
Disable, Enable
Disable
Disable, Enable
Enable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable