Huawei UPS5000-A User Manual page 178

60 kva-120 kva
Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(60 kVA-120 kVA)-H
User Manual
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0087-1
System
transfer-to-
bypass
0089-1
Rack output
overload
0090-1
Dry contact
board fault
0090-2
0356
Battery Mode
0359
No power
supplied
0332
Output
disabled
0334
BSC master
system
0334
BSC slave
system
0342
Mains input
breaker open
0343
BPM input
breaker open
0340
The
maintenance
circuit breaker
is ON.
0335
Generator
connected
0594-1
Insufficient
Issue 05 (2020-01-10)
Severity
Cause
load impact.
Warning
The neighboring UPS
is not normal, and
transfers to bypass
mode.
Minor
The load is excessive.
Critical
I2C communication
with the dry contact
board MUE05A fails.
I2C communication
with the dry contact
board MUE06A fails.
Minor
The UPS is working
in battery mode.
Warning
No power is supplied.
Minor
The output is
disabled.
Warning
BSC master system.
Warning
BSC slave system.
Critical
The mains input
circuit breaker is
OFF.
Critical
The bypass input
circuit breaker is
OFF.
Minor
The maintenance
circuit breaker is ON.
Warning
The generator is
connected.
Minor
The load is
Copyright © Huawei Technologies Co., Ltd.
Solution
Check the reason why the neighboring
UPS transfers to bypass mode.
Check the load. Remove some loads
or expand the UPS power capacity if
the UPS is overloaded.
Replace the dry contact board
MUE05A.
Replace the dry contact board
MUE06A.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
Running status displayed. No
suggested measures.
1. Reduce the load.
B Alarm List