Torque Specifications; Table 16 - Expected Ac Voltage Range; Table 17 - Motor Terminal Block Torque Specifications; Figure 51 - Measuring Ac Input Voltage - Danfoss Turbocor VTT Series Service Manual

Variable twin turbo compressors
Table of Contents

Advertisement

Figure 51 - Measuring AC
Input Voltage
Table 16 - Expected AC
Voltage Range
3.3.3.3 Torque
Specifications
Table 17 - Motor
Terminal Block Torque
Specifications
Compressor Components
3. Place the meter probe on one phase of the AC input posts and the other meter probe on
another phase of the AC input as shown in Figure 51 (Measuring AC Input Voltage).
4. Verify that the meter shows the expected AC measurement within the range as indicated in
Table 16 (Expected AC Voltage Range).
VFD Module
N165 T5
N232 T5
N262 T5
5. If the meter does not show any reading, it is possible that there is no power from the VFD.
Measure again but this time verify the 3-phase output at the VFD.
6. If the meter still does not show any reading, ensure the AC power source is turned ON and try again.
7. If the measured values correspond to the specified values for all phases, the AC input voltage is okay.
Power Cover, SHCS, M5x16
Motor Terminal Block to Compressor, SHCS, M5x20
Tower Feed Through Nut, Brass M16x1.5
Power Cable Nut, Brass M10x1.5
Bus Bar Mounting, SHCS, M5x16
Ground Cable Nut, M10x1.5, Brass
Nominal Voltage
380
400
460
380
400
460
380
400
460
Description
AC Input Posts
(3 places)
Acceptable Voltage Range
342-418
360-440
414-506
342-418
360-440
414-506
342-418
360-440
414-506
Nm
Ft.Lb.
6
5
6
5
20
15
10
8
5
4
20
15
M-SV-VT-001-EN Rev. A
In.Lb.
53
53
177
89
44
177
57 of 165