Figure 78 - 24 VDC
Connector at CIM
3.7.1.3.2 24 VDC CCM-CIM
Cable Verification
3.7.1.4 DC-DC-CCM
24V Cable
Figure 79 - DC-DC-CCM
Cable (Revisions A and
B)
78 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
4. Remove the cover to the controls panel where the CIM is located.
5. Remove the 24 VDC connector from the CIM.
J7
1
AUX P/T SENSORS
24VDC
CCM CAN
POWER
1
J2
J1
1
24 VDC
Connector
There are two (2) variants of the CIM. Revisions A and B do not contain the connector numbers
(e.g., J5). The "Pin 1" indicators are also not present on the A and B revisions.
6. Route the cable out of the service side and CIM boxes.
Installation:
1. Route the new cable between the CCM and CIM.
2. Insert the 24 VDC connector to the CIM.
3. Insert the 24 VDC connector into J7 on the CCM Board.
4. Replace the covers.
5. Restore power to the Compressor.
After power is applied to the Compressor, ensure the light emitting diodes (LEDs) on the CIM are on
and communication is established.
The DC-DC-CCM 24V Cable passes 24 VDC from the DC-DC to the CCM.
J6
1
Comm
Reset
STAGING
VFD COOLING
I-Lock
USB
CAN
I-Lock
Status
Status
1
COMPRESSOR INTERFACE MODULE
NOTE
J5
RUN
1
Fault
Fault
EV
Reset
Status
STATUS
RS485-1
RS485-2
TX
J3
RX
1
J4
TX
RX