Application guidelines VZH088-117-170 single compressors Single compressors VZH scroll specificities .........................6 Variable speed compressors ........................7 Compressor size ......................................7 Frequency converter variants .................................7 Compressor and frequency converter combinations ........................7 Nomenclature and specifications ......................8 Compressor nomenclature ..................................8 Frequency converter nomenclature ..............................8 Technical specifications ........................9 Compressor specifications ..................................9 Frequency converter specifications ..............................9 Oil injection control ....................................9...
Page 5
Application guidelines VZH088-117-170 single compressors Single compressors Operating conditions .........................43 Application envelopes .................................... 43 Short cycle timer function ..................................43 Discharge gas temperature protection function .......................... 44 Discharge gas thermostat ..................................44 Oil return management function (single compressor) ....................... 45 Oil return management in hybrid manifolding ..........................
Application guidelines VZH scroll specificities Single compressors Reinforced high grade cast iron scroll set. 2 ranges for high and low pressure ratio High speed oil circulation minimized by separating oil and gas flows with a sump oil return tube A patented oil injection system ensures optimal efficiency at low speed by improving scroll set sealing...
Application guidelines Variable speed compressors Single compressors Compressor size Variable speed offers more flexibility in 3. Best Seasonal Efficiency Ratio: Select a compressor selection than fixed speed compressor size which achieves the minimum system cooling demand at its minimum speed. compressors.
Application guidelines Nomenclature and specifications Single compressors Compressor nomenclature Variable speed Evolution index Motor protection type Family N: no internal motor protection VZH scroll (protection by drive) Lubricant Equipement version POE lubricant, R410A A: brazed connections, single version refrigerant B: brazed connections, manifold version Oil sight glass Oil level switch Swept volume...
This connection is VZH088 Rotolock 1"3/4 used when compressors are mounted in parallel. VZH117 Rotolock 1"3/4 Contact Danfoss for further details and refer to VZH170 Rotolock 2"1/4 hybrid manifolding specific section at the end of this document. Oil drain fitting VZH170 are equipped with oil drain connection.
Page 30
Application guidelines Dimensions Single compressors CDS303 frequency converter - enclosure B2 380-480 volts – 18-22 kW - IP55 housing 34 (1.34) (7.09) 37 (1.46) 43 (1.7) 30 (1.18) 84 (3.31) (0.43) 9 (0.35) (1.57) (0.47) (0.35) Min 200 (7.87) (10.24) Ø19 Air space outlet (0.75)
Page 31
Application guidelines Dimensions Single compressors CDS303 frequency converter - enclosure B3 380-480 volts - 15 kW - IP20 housing (0.31) (0.27) (0.31) Ø12 (0.47) Scale 1:2 Min 100 (3.94) 165 (65) Air space outlet 140 (5.51) (9.80) Air outlet (15.71) (16.53) (14.96) Mounting base...
Page 32
Application guidelines Dimensions Single compressors CDS303 frequency converter - enclosure B4 380-480 volts – 18-22 kW - IP20 housing 200-240 volts – 15 kW - IP20 housing 525-600 volts - 18-30 kW - IP20 housing 0.33 (9.05) Min 200 (7.87) (0.59) (9.53) air space outlet...
Page 33
Application guidelines Dimensions Single compressors CDS303 frequency converter - enclosure C1 200-240 volts – 15-18-22 kW - IP55 housing (0.38) (0.35) (0.47) (0.74) scale 1:2 Min 200 (12.20) Air space outlet (10.70) (12.12) Air outlet (26.77) (25.51) Min 200 Mounting base (0.39) Air inlet Air space inlet...
Page 34
Application guidelines Dimensions Single compressors CDS303 frequency converter - enclosure C3 200-240 volts – 18-22 kW - IP20 housing (0.33) (0.67) (12.13) Min 200 (7.87) (13.11) Air space outlet (1.42) (10.63) Air outlet (19.21) (20.51) (24.80) (21.65) Air intlet Min 200 (7.87) Air space intlet (0.47) Dimensions in mm (inch)
Application guidelines Electrical data, connections and wiring Single compressors Supply voltage Because VZH compressors are powered by a = 0.87* I frequency converter, the mains frequency, 50 or = 1.05* I 60 Hz, is no longer an issue. Only the mains = 0.90* I voltage is to be taken into account.
Application guidelines Electrical data, connections and wiring Single compressors Fuses / circuit breakers Danfoss recommends using the fuses/circuit and are recommended. Other types of circuit breakers listed below to protect service breakers may be used provided they limit the energy to a level equal to or lower than the personnel and property in case of component break-down in the frequency converter.
Application guidelines Electrical data, connections and wiring Single compressors Wire sizes Below table lists recommended wiring sizes for the motor compressor power supply cables. These wiring sizes are valid for a cable length up to 65 ft. from drive to from network to compressor to drive...
Application guidelines Electrical data, connections and wiring Single compressors EMC correct installation of an IP20 frequency drive CDS303 EMC qualification reports are available upon request to Danfoss technical support. PLC etc. Panel Grounding rail Cable insulation stripped Min. 0.025 in ²...
Application guidelines Electrical data, connections and wiring Single compressors Wiring connections T1/U T2/V T3/W Ana out COM Ana out + Ana out +10 V 230V or 24V Ana in 0 ± 10 V ~ Ana in 0 ± 10 V 2 A max Ana in COM +24V...
Application guidelines Electrical data, connections and wiring Single compressors Electrical connections Electrical power is connected to the compressor The cable gland has to be of EMC design to terminals by Ø 3/16” (4.8 mm) screws. The guaranty a good grounding of the armored cable. maximum tightening torque is 3 Nm.
Application guidelines Operating conditions Single compressors Application envelopes The operating envelopes for VZH scroll • Minimum suction superheat should be above compressors are given in the figures below, 5K and minimum sump superheat should be above 10K due to the risk of liquid flood back. where the condensing and evaporating temperatures represent the range for steady state operation.
Application guidelines Operating conditions Single compressors Discharge gas temperature A discharge temperature monitor function can be To activate the discharge temperature monitor protection function enabled in the frequency converter. All settings function, with the factory setting, the only modification required is to connect the sensor are available in parameter list 28.2x, they are factory preset as follow: to Analog Input 54 (4 - 20 mA) between 13 and...
Insulation Bracket A DGT accessory is available from Danfoss: refer to accessories pages at the end of this document. Oil return management Insufficient oil level can be the result of oil 3000 rpm (50 rps) for too long (as programmed in function (single compressor) depositing itself in pipes and heat exchangers.
Page 46
(except with pump-down). Danfoss recommend to use ETS products. EXV should be closed, and remained closed, Ramp-up and ramp-down settings, of both EXV and compressor, must be done with great care.
Application guidelines System design recommendations Single compressors Essential piping design The working pressure in systems with R410A is flow will be lower compared to R22/R407C considerations about 60% higher than in systems with R22 or systems. To maintain acceptable pressure drops and acceptable minimum gas velocities, R407C.
In order to prevent compressors from breaking piping (long line set, U trap…), multiple heat down due to oil level issues, Danfoss requires the exchangers and elevation changes. use of an oil separator in all long piping systems, particularly for split systems.
Page 49
(Orifice Φ2.0) code number 018F6257 “24V (CE)” 50Hz AC” specification 1m 3-core cable solenoil coil code number 018F6282 “220-230V 50/60Hz AC” specification 1m 3-core cable Customers can of course contact Danfoss application engineers for support regarding recommendations in such systems. FRCC.PC.023.A7.22...
More detailed information can be found in the compressor is limited. In this respect, follow the paragraphs hereafter. Please contact Danfoss guidelines given in the section: “Essential piping technical support for any deviation from these design recommendations”...
Application guidelines System design recommendations Single compressors VZH scroll compressors can tolerate occasional Off-cycle migration can be prevented by flooded starts as long as the total system charge implementing a crankcase heating or adding a does not exceed the maximum compressor pump-down cycle to the operation cycle and a refrigerant charge limit.
12 K above the ambient temperature for air cooled condensers. reaches a satisfactory level. Note: The minimum condensing pressure must For further information, please contact Danfoss be set at the minimum saturated condensing Technical support. temperature shown in the application envelopes.
Application guidelines Specific application recommendations Single compressors An oversized valve may result in erratic control. • The compressors should be run for a minimum period in order to ensure that the This can lead to liquid refrigerant entering the compressor if the expansion valve does not oil has sufficient time to properly return to provide stable refrigerant super-heat control the compressor sump and that the motor has...
4 way valve position 2 minimum pressure for 4 way valve moving. Danfoss recommend above defrost cycle logic, 10" 2" 10" 2" In order to limit liquid amount handled by but the control logic is also system specified.
Page 55
Application guidelines Specific application recommendations Single compressors The use of a suction line accumulator is strongly Sustained and repeated liquid slugging and Suction line accumulator recommended in reversible-cycle applications. floodback can seriously impair the oil’s ability to lubricate the compressor bearings. This situation This because of the possibility of a substantial quantity of liquid refrigerant remaining in the can be observed in wet climates where it is...
Acoustic hoods are available from Danfoss as accessories. These hoods are quick Use of sound-insulation materials on the inside of and easy to install and do not increase the overall unit panels is an effective means of substantially size of the compressors to a great extend.
Application guidelines Sound and vibration management Single compressors Speed by-pass If vibrations occurs at some typical frequencies speed by-pass is adjustable in the frequency of the VZH variable speed compressor system, converter, in order to avoid some frequency ranges. Four by-pass ranges are adjustable, and design must be checked: frame, piping, pipes using cushioned clamps.
Application guidelines Installation Single compressors Each compressor is shipped with printed http://instructions.cc.danfoss.com instructions for installation. These instructions can also be downloaded from: Compressor handling Each VZH scroll compressor is equipped with When the compressor is mounted as part of two lift rings on the top shell. Always use an installation, never use the lift rings on the both these rings when lifting the compressor.
(water content capacity), For servicing of existing installations where acid the system refrigeration capacity and the system formation is present the Danfoss DCL solid core refrigerant charge. Brazing and soldering When brazing copper-to-copper connections, temperature of below 800°C is recommended.
Page 60
For more detailed information on the appropriate draw the brazing material into the joint, but not materials required for brazing or soldering, please into the compressor. contact the product manufacturer or distributor. For specific applications not covered herein, please contact Danfoss for further information. FRCC.PC.023.A7.22...
Application guidelines Installation Single compressors High voltage test On M Ohm 2000 M Ohm M ohm 200 2000MOhm 20 ohm M ohm Gossen - ISOWID - 0413 MOTOR - 24V + - DC +DC It is not necessary to perform a Hipot test •...
The best location is on the Refer to news bulletin FRCC.EN.050 “Danfoss liquid line between the condenser outlet and the Commercial Compressors recommended filter drier.
If any deviation is observed, this means that some oil is trapped in the system, heat exchangers and/or pipes. Always use original Danfoss POE oil 160SZ from new cans. The CDS303 frequency converter integrates an oil recovery management algorithm which needs Top-up the oil while the compressor is idle.
Setting Error(s) cable Check VZH Come back to Motor resistance factory settings and isolation Correct Incompatibility the fault Between Software & Mains shut-off Additional option before checking ! Contact your Local Danfoss Reset & start March, 2014| Commercial Compressors FRCC.PC.023.A7.22...
Page 65
Check main power supply Check power voltage supply voltage Power normal Set 14-11 to lower value Internal components damage Too high or Reset & start too low Contact your Local Danfoss Turn off power Reset & start March, 2014| Commercial Compressors FRCC.PC.023.A7.22...
Page 66
Application guidelines Troubleshooting Single compressors Check alarm # (Continue) Start failed Speed limit (low) Wrong wiring of U/V/W Minimum speed not reached after 2 sec. Compressor bearing wear Compressor stopped, similar reason as A49 Compressor stopped Automatic restart after 30s Automatic restart after 30s 10 restarts...
Application guidelines Ordering information and packaging Single compressors Kit ordering and shipping The tables on the following pages give code compressor and CDS303 frequency converter kit numbers for ordering purposes for the VZH packed and shipped separately. Packaging Compressor single pack Height Width Depth...
Page 68
Application guidelines Ordering information and packaging Single compressors X = Motor code Compressors industrial pack Compressor model Technical Name Code G Code J VZH088AXANA 120G0078 120G0080 VZH088BXANA 120G0079 120G0081 VZH088 VZH088AXBNA 120G0090 120G0092 VZH088BXBNA 120G0091 120G0093 VZH117AXANA 120G0082 120G0084 VZH117BXANA 120G0083 120G0085 VZH117...
Application guidelines Ordering information and packaging Single compressors VZH voltage code G - 380-480 Volt Frequency converter Compressor model Code n° for Model & power IP class RFI class Coating ordering 134G3576 134G3577 IP20 134F9366 134G3578 CDS303 VZH088-G 15.0kW 134G4008 134G4010 IP55 134G4012...
Application guidelines Ordering information and packaging Single compressors VZH voltage code J - 200-240 Volt Frequency converter Compressor model Model & power IP class RFI class Code n° for ordering 134G3474 IP20 134F9361 CDS303 VZH088-J 15.0kW 134G4001 IP55 134G4002 134G3585 IP20 134F9363 CDS303...
Application guidelines Accessories Single compressors Mounting kits Type Code n° Description Application Packaging Pack size Mounting kit for 1 scroll compressor including 4 grommets, 4 120Z0066 VZH088-117 Single pack sleeves, 4 bolts, 4 washers Mounting kit for 1 scroll compressor including 4 grommets, 4 8156138 VZH170 Single pack...
Page 73
Application guidelines Accessories Single compressors Fans Pack Type Code n° Description Application Packaging size 130B3406 Fan IP55 VZH117 G & J Single pack 1 Control card Pack Type Code n° Description Application Packaging size 130B1109 Control card Frequency converter / all models Single pack Accessory bags Pack...
Page 74
Application guidelines VZH088-117-170 - hybrid manifolding Manifold compressors General overview ..........................75 Scope ..........................................75 Benefits......................................... 75 Oil management concept ........................76 Systems ........................................76 Oil separator ....................................... 78 Approved hybrid tandem configurations and capacity range ....................80 System design recommendation .......................81 Electronic expansion valve ...................................
Danfoss SH fixed speed compressor and VZH Application Guidelines for single compressors. Variable speed compressor in air conditioning and heat pump applications.
VZH and SH compressors by Danfoss is designed in an innovative way which is Considering oil return risk, split system robust with any kind of upstream piping. with more than 10m piping length need mandatory application approval by Danfoss application specialists.
Page 77
Application guidelines Oil management concept Manifold compressors A restrictor is used in suction line of either fixed make sure fixed speed have reasonable oil level speed or inverter to well balance the low side at this condition. That means when inverter run at any frequency below 100 rps, the fixed speed pressure between Variable speed and fixed speed compressors when fixed speed is ON and...
Chiyoda (CE marked) oil separator (OS) since it equipment configurations and accessory options. has been tested by Danfoss. Chiyoda OS could improve oil starvation with selected capillary size, Many oil separator design exist; the selection,...
Page 79
VZH170+SH295 VZH: ID Ø1.8*1380 mm*mm SH: ID Ø1.8*1600 Strainer Mesh size Orifice(mm) Φ2.0 Solenoid Code number 032F1201 valve Model: Connection(in) 1/4" Danfoss (Orifice Code 018F6257 Φ2.0)(CE) number 50Hz AC Specification 1m 3-core cable Solenoid coil Code 220-230V 018F6282 number 50/60Hz...
179.3 51.0 ARI conditions: 7.2/54.4/11.1/8.3°C The kit available for these tandems are tested with Danfoss recommended piping design. If the piping G motor code: 380-480V/3ph/50-60Hz is customized by the customer, additional test to check oil balancing must be performed. Please contact your Danfoss Application Specialist for support.
The pump down pressure switch must have a set compressors. Please refer to the chapter on VZH point slightly higher than the lowest compressor single compressors and the Danfoss SH single safety pressure switch set point. The high- compressors application guidelines (reference pressure safety pressure switch shall stop all FRCC.PC.007) for recommended settings.
12 reduces the service life of the motor compressor unit. If necessary, place an anti-short- cycle timer in the control circuit, connected as shown in the wiring diagram in the Danfoss SH scroll compressors application guidelines. A 4-minute timeout is recommended.
Frame compressors. Compressor mounting For VZH tandem systems, Danfoss supply both Regarding rubber connection, compressors rigid and rubber connections, but only rubber are mounted on the base with enough stiff by connection is recommended by Danfoss. For grommets.
Therefore a installation (i.e. : oil analysis). Oil equalisation connection Danfoss Commercial Compressors has developed 1-1/8” oil equalisation line specially adapted oil equalisation • SH180 to 380: 2”1/4 rotolock connection allowing the use of 2”1/4 - 1”3/8 Organ pipe...
+1 x new manifolding kit(120Z0591)+1x voltage. rubber mounting kit(8156138) Please note for VZH170 hybrid manifolding, Danfoss VZH and SH scroll compressors can rigid spacers is delivered with compressor be ordered in either industrial packs or in SH180/240/295 please leave rigid connection single packs.
Page 86
Application guidelines Ordering information Manifold compressors Manifolding kit 230V Type Code Number 230VAC/ VDC type New code number 120Z0594 120Z0595 120Z0596 120Z0597 120Z0598 120Z0599 120Z0600 120Z0601 VZH088+ VZH088+ VZH117+ VZH117+ VZH117+ VZH170+ VZH170+ VZH170+ Description SH090 SH120 SH140 SH161 SH184 SH180 SH240 SH295...
Application guidelines VZH088 Manifold compressors Composition of VZH088 tandem Composition Tandem model Variable speed Fixed speed VZH088 + SH090 VZH088 SH090 VZH088 + SH120 VZH088 SH120 7/8" Discharge left 1"3/8 Suction left 1"5/8 1"1/8 See detail A 240 Mini 1"1/8 Mini Oil equalization 1"1/8...
Application guidelines VZH088 Manifold compressors Compressor mounting The tandem is fixed on the frame using the Because VZH088 is 0.28 inch smaller than flexible grommets supplied with the compressor. SH120 and in order to have the oil equalisation connection at the same level for both The compressors are fixed on the rails (not compressors, an additional 0.28 inch rigid spacer included) using rubber grommets, mounting...
Application guidelines VZH088 Manifold compressors Suction washer Due to the difference of capacities of the compressors, it is essential to equalise the pressure of the sump. But, this oil equalisation or is also function of the configuration of the suction pipe. Suction washer is on fixed speed compressors.
Application guidelines VZH117 Manifold compressors Oil equalisation connection The level of oil is naturally balanced by a 1”1/8 oil equalization line. The kit 120Zxxxx includes a 1”3/4 to 1”1/8 adaptor sleeve (4) & a teflon seal (5) to connect the oil line to the compressor 1”3/4 oil connector ...
Application guidelines VZH170 Manifold compressors Oil equalisation connection The level of oil is naturally balanced by a 1"3/8 oil equalization line. The plastic organ pipe (1) connected to the fitting (2) is preinstalled in the compressor. Oil line (3) is brazed to the sleeve (4).
Page 94
Application guidelines Updates Previous version Current version • Page 28: Frequency converter dimensions • Page 28: Added Bracket supplied to Frequency converter dimensions table. • Page 42: Approvals and certificates • Page 42: Added Low voltage directive 2014/35/ EU to Approvals and certificates. •...