• Best Seasonal E ciency Ratio: select a compressor size that achieves the minimum Performance The Danfoss VRJ compressors referenced in this A seventy-two hour run-in is recommended to guide is a fully compliant scroll and actually meet performance expectations.
Compressor model designation Application Guidelines Application, Swept Model Voltage Motor Equipment Other Nomenclature Family Volume Variation Protection Version Features & Refrigerant Application, Family Other features & refrigerant 6: No other features V: Variable speed Equipment version R: Residential P: Brased connections, J: R410A, PVE lubricant spade terminals Motor protection...
(I) Variable speed drive For dedicated variable speed drive speci cations, speci cations refer to “Danfoss VRJ Installation and Operation instructions”. Bearings lubrication A speci c oil pump ensures optimal bearing as avoid excessive Oil Circulation Ratio (OCR) at lubrication at all compressor speeds.
0.254 LRA (Locked Rotor Amp) LRA is the higher average current as measured VRJ compressors, the LRA value is low because the on a mechanically blocked compressor tested variable speed drive reacts very rapidly (far below under nominal voltage. LRA is printed on the 1 second).
Application Guidelines Electrical data, connections and wiring Wiring connections VRJ scroll compressors will only compress gas while rotating counter-clockwise (when viewed from the compressor top). The drawing shows electrical terminal labelling and should be used as a reference when wiring the compressor.
Application Guidelines Approvals and certificates Approval and certi cates VRJ scroll compressors comply with the following approvals and certi cates. All models (Underwriters Laboratories) Other approvals / certi cates Contact Danfoss Pressure equipment Refrigerating uids Group 2 directive 97/23/EC Category PED...
Polyvinyl ether (PVE) is an innovative refrigeration The compressor technology applied in Danfoss lubricant for HFC refrigerant systems. PVE is as VRJ scroll compressors in combination with PVE hygroscopic as existing polyolester lubricants lubricant provides the best possible result in (POE), but PVE does not chemically react with terms of reliability and compressor lifetime.
900 - 4500 RPM Saturated evaporating temp. (°F) Maximum discharge gas The discharge temperature depends mainly on Refer to “Danfoss VRJ Installation and Operation temperature the combination of evaporating temperature, instructions” for connection details, and to condensing temperature and suction gas “Sensor Selection Guideline”...
Application Guidelines Operating conditions High and low pressure Suction and discharge pressure transmitters have Refer to “Danfoss VRJ Installation and Operation protection to be installed and connected to the variable instructions” for connection details, and to speed drive to ensure the compressor operates “Sensor Selection Guideline”...
Start-up sequence To ensure correct lubrication of all the for some seconds. Then the compressor speed mechanical parts, VRJ compressors start with increases up to the desired set point according to a de ned ramp-up, and stay at a xed speed capacity request.
Application Guidelines System design recommendations General Successful application of scroll compressors beyond the limits given in this manual. Poor is dependent on careful selection of the performance, reduced reliability, or both may compressor for the application. If the compressor result. is not correct for the system, it will operate Essential piping design Proper piping practices should be employed to...
Saturated suction temp. °F Preventing liquid ood back Danfoss recommends the use of an electronic Exceptions to the use of EXV’s with Danfoss expansion valve for all air conditioning and heat VRJ must be approved by Danfoss application pump applications with VRJ compressors. An engineering.
Loss of charge protection VRJ scroll compressors together with the variable speed drive include a loss of charge protection drive. function. This protection is ensured if pressure...
The VRJ scroll compressor is designed to be quiet and the frequency of the sound generated is Because of the Danfoss unique design of a full- pushed into the higher ranges, which not only suction gas &...
Page 19
If vibrations still occur at some typical some frequency ranges and avoiding vibrations frequencies, a speed bypass function is available to occur. Refer to “Danfoss VRJ Installation and within the VRJ. This function allows avoiding Operation instructions” for setting details.
Application Guidelines Installation Each VRJ scroll compressor is shipped with printed Instructions for installation. System cleanliness The refrigerant compression system, regardless System contamination is one of main factors a ecting equipment reliability and compressor of the type of compressor used, will only provide high e ciency and good reliability, along with a service life.
• Purge nitrogen or CO2 through the The PVE oil used in VRJ compressors is highly compressor in order to prevent against hygroscopic and will rapidly absorb moisture oxidation and ammable conditions. The from the air.
Remove and replace the liquid line lter burnout drier and the liquid line and suction line drier and install a Danfoss type DAS burnout drier lter driers. of appropriate capacity. AB141686422149en-US0401...
Compressors are packed individually in a cardboard box. They can be ordered in any quantity. Minimum ordering quantity = 1. As far as possible, Danfoss will ship the boxes on full pallets of 9 compressors. Each box contains following accessories: •...
Need help?
Do you have a question about the VRJ and is the answer not in the manual?
Questions and answers