Figure 18 - IFV Actuator

3.2.2.1 Removal and
Installation
Figure 19 - IFV Actuator
Mounting Set Screws
32 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
IFV Actuator Removal:
1. Isolate the Compressor power as described in the
section of this manual.
2. Disconnect the Red (power) and Black (signal) cables from the IFV by turning the collars, located
on the cable ends, in a counter-clockwise rotation.
3. Using a 2.5 mm hex bit, loosen the three (3) set screws that attach the IFV Actuator to the
Bonnet/Function Module.
4. Remove the IFV Actuator.
"Electrical Isolation of the Compressor/VFD"
Set Screw - 3 Nm (27
in.lb.) (3 places)