Removal And Installation; Figure 100 - Rear Bearing Sensor Connections - Danfoss Turbocor VTT Series Service Manual

Variable twin turbo compressors
Table of Contents

Advertisement

3.7.1.8.1 Removal and
Installation
Figure 100 - Rear Bearing
Sensor Connections
88 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Removal:
1. Isolate the Compressor power as described in the
section of this manual.
2. Remove the Service Side Cover.
3. Remove the 9-pin connector from J10 on the CCM Board.
4. Remove the Molex connector from J1 on the CCM Board.
5. Twist and pull to remove the sensor cable connection from the feed through.
"Electrical Isolation of the Compressor/VFD"