Removal And Installation; Figure 70 - Thermal Paste Application - Danfoss Turbocor VTT Series Service Manual

Variable twin turbo compressors
Table of Contents

Advertisement

3.7.1.1 Removal and
Installation
Figure 70 - Thermal
Paste Application
Thermal Paste
Application Location
Follow established ESD procedures to prevent damage to sensitive electronic components when
working on the Service Electronics Assembly.
The CCM and PWM Boards cannot be serviced separately, therefore the Service Electronics Assembly
will need to be replaced should there be a fault with either the CCM or the PWM.
Removal:
1. Isolate the Compressor power as described in the
section of this manual.
2. Remove the Service Side Cover.
3. Disconnect the power and communications cables from the CCM and PWM.
4. Disconnect all cables going to the VTT Service Electronics Assembly.
5. Remove the PWM heat sink fasteners and ground wires (if applicable).
The various connections are illustrated throughout this section.
6. Remove the fasteners that secure the Service Electronics Assembly plastic frame to the main
housing and then remove the Service Electronics Assembly.
Installation:
1. Clean the Compressor housing and apply a thin layer of thermal paste to the PWM heat sink
surface of the main housing. Refer to Figure 70 (Thermal Paste Application).
• • • CAUTION • • •
"Electrical Isolation of the Compressor/VFD"