Cim Verification; Removal And Installation; Torque Specifications; Table 36 - Cim Torque Specifications - Danfoss Turbocor VTT Series Service Manual

Variable twin turbo compressors
Table of Contents

Advertisement

6.1.1 CIM Verification

Figure 199 - Active Alarm/
Fault Viewer
6.1.2 Removal and
Installation
6.1.3 Torque
Specifications
Table 36 - CIM Torque
Specifications
OEM Module Components
1. With power applied to the compressor, connect to the CIM using the SMT and enter the User ID
and Access Code.
2. Open the Warnings and Faults Tool.
3. Verify that the CIM Compatibility, CAN Communications, and VFD Communications Faults are
not active.
Removal:
1. Isolate the Compressor power as described in the
section of this manual.
2. Remove all terminal connectors from the original CIM, leaving all wires connected to the
screw terminals.
3. Remove the CIM from the DIN Rail (or other mounting method).
4. Remove the DIN Rail clip (or other mounting method) from the CIM.
Installation:
1. If used with the original CIM, install the DIN Rail clip (or other mounting method) on the new
CIM, using the original hardware.
2. Mount the new CIM in place.
3. Reinstall all terminal connectors to their proper location.
4. Reconnect power to the compressor.
DIN Rail Clip, SHCS, M4x10
Ground Screw
"Electrical Isolation of the Compressor/VFD"
Description
Nm
Ft.Lb.
3
-
6
-
M-SV-VT-001-EN Rev. A
In.Lb.
27
53
151 of 165