Table 20 - Stator Thermistor R/T Curve - Danfoss Turbocor VTT Series Service Manual

Variable twin turbo compressors
Table of Contents

Advertisement

Table 20 - Stator
Thermistor R/T Curve
66 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Temperature
Resistance
º C
-50
803.1
-40
842.7
-30
882.2
-20
921.6
-10
960.9
0
1000.0
10
1039.0
20
1077.9
30
1116.7
Measured values must be within ± 10% of the values in Table 20 (Stator Thermistor R/T Curve).
9. Verify resistance of each circuit at the external connector to housing (ground).
• Should be "open. "
10. If the Stator Temperature Sensor Feed Through is suspected to have a problem, remove it and
test as above directly at the internal connector. Refer to the
Through"
section of this manual.
11. Restore power to the Compressor.
Temperature
Resistance
º C
40
1155.4
50
1194.0
60
1232.4
70
1270.8
80
1309.0
90
1347.1
100
1385.1
110
1422.9
120
1460.7
NOTE
"Stator Temperature Sensor Feed
Temperature
Resistance
º C
130
1498.3
140
1535.8
150
1573.3
160
1610.5
170
1647.7
180
1684.8
190
1721.7
200
1758.6

Advertisement