3.2.5 Pressure/
Temperature Sensor
Cable Harness
Figure 28 - Pressure/
Temperature Harness
3.2.5.1 Removal and
Installation
Figure 29 - J8 CCM Board
Connector
Compressor Components
The Pressure/Temperature Sensor Cable Harness connects the two (2) combination pressure/
temperature sensors to the CCM.
Pressure/Temperature Sensor Cable Harness Removal:
1. Isolate the Compressor power as described in the
section of this manual.
2. Remove the Service Side Cover.
3. Unplug the cable harness connector from the suction and discharge sensors.
4. Unplug the cable harness connector from J8 on the CCM. Refer to Figure 29 (J8 CCM Board
Connector).
5. Remove the cable harness from the Compressor retaining clips. Refer to Figure 30 (Pressure/
Temperature Sensor Harness Retaining Clips).
"Electrical Isolation of the Compressor/VFD"
J8 Connector
M-SV-VT-001-EN Rev. A
39 of 165
Need help?
Do you have a question about the Turbocor VTT Series and is the answer not in the manual?
Questions and answers