Pre-Installation Steps
Pre-Installation Steps
Ventilate the Spray Booth
Provide fresh air ventilation to avoid the buildup of
flammable or toxic vapors when spraying, flushing,
or cleaning the applicator. Do not operate the
applicator unless ventilation air flow is above the
minimum required value..
Electrically interlock the Electrostatic Controller (A)
with the ventilators to prevent applicator operation
unless ventilation air flow is above the minimum
required value. Use the 24 VDC Interlock pin on
the Discrete I/O cable to connect to the ventilator
interlock. Check and follow all National, State,
and Local codes regarding air exhaust velocity
requirements.
NOTE: High velocity air exhaust will decrease the
operating efficiency of the electrostatic system. The
minimum allowable air exhaust velocity is 60 ft/minute
(19 linear meters/minute).
14
Install the Rotary Applicator
See the Rotary Applicator Manual (334452 or
334626) for installation instructions.
Interlock the Isolation Enclosure
(Waterborne Only)
To reduce the risk of electric shock, interlock the
Electrostatic Controller with the voltage isolation
system to shut off the electrostatics anytime the
isolation system enclosure is opened.
For information about the interlocks and their use,
see
Interlocks, page 7
.