4.7 Relay Operation Control Menu

SELECT
CHG
This menu allows you to set the relay operation mode: non-failsafe or failsafe.
Failsafe relay operation is the opposite of normal operation where relay contacts
are closed when a relay is operated (activated), and are open when a relay is
released (de-activated). In failsafe mode, an alarm is activated by a non-
energized relay which will open in all cases when an alarm condition is present
or an alarm setpoint is not operational either due to a loss of control power or
due to corruption of the setpoint setup configuration. A failsafe relay is closed
only if it is under setpoint control and no alarm conditions exist, or if it is manually
operated via communications.
rELo
rEL.1
nor
NOTES
1.
You will not be able to change the relay operation mode if a relay has been allocated
for pulsing.
2.
When a failsafe relay is allocated for pulsing, it automatically reverts to normal
operation.
32
ENTER
To select a relay:
SELECT
Press
to activate the middle window, and then use
the up/down arrow keys to scroll to the desired relay.
To change the relay operation mode:
SELECT
Press
to activate the lower window.
Use the up/down arrow keys to set the desired option.
Select nor for normal (non-failsafe) relay operation, or
select FSAFE for failsafe relay operation.
ENTER
Press
to store your new setting or press
leave your previous setting unchanged.
To quit the setup menu:
From the middle window, press
rELo
ENTER
to
ESC
ENTER
ESC