Configuration Of The As-I Master; Overview Of The Commands; Set Operation Mode (Set_Op_Mode: Set_Operation_Mode) - Pepperl+Fuchs VBG-PB-K25 Manual

As-i/profibus gateway in acc. to specification 3.0
Table of Contents

Advertisement

8.2.4

Configuration of the AS-i Master

8.2.4.1

Overview of the Commands

comamnd
SET_OP_MODE
STORE_CDI
READ_CDI
SET_PCD
GET_PCD
SET_LPS
GET_LPS
STORE_PI
WRITE_P
READ_PI
SET_PP
GET_PP
SET_AAE
8.2.4.2

Set Operation Mode (SET_OP_MODE: Set_Operation_Mode)

This call switches between configuration mode and protected mode.
In protected mode, only AS-i slaves entered in the LPS and whose expected and
actual configurations match, are being activated.
In other words: The slaves are being activated if the I/O configuration and the ID
codes of the detected AS-i slaves are identical to the configured values.
In configuration mode, all detected AS-i slaves (except for AS-i slave "0") are ac-
tivated. This also applies to AS-i slaves for which there are differences between
the expected and actual configuration.
The "OPERATION MODE" bit is stored permanently; in other words, it is retained
after a cold/warm restart.
When you change from configuration mode to protected mode, the AS-i master will
do a warm restart (change to the offline phase followed by a change to the online
mode).
If an AS-i slave with address "0" is entered in the LDS, the AS-i/PROFIBUS
gateway cannot change from configuration mode to protected mode.
Subject to reasonable modifications due to technical advances.
60
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Values for command
value meaning
0C
Set_Operation_Mode
16
07
Store_Actual_Configuration
16
28
Read_Actual_Configuration
16
25
Set_Permanent_Config
16
26
Get_Permanent_Config
16
29
SET_LPS
16
44
Get_LPS
16
04
Store_Actual_Parameter
16
02
Write_Parameter
16
03
Read_Parameter
16
43
Set_Permanent_Parameter
16
01
Get_Permanent_Parameter
16
0B
Set_Auto_Adress_Enable
16
AS-Interface
Command Interface
Req Len Res Len
3
2
3
5
3
11
2
2
4
3
4
3
3
Copyright Pepperl+Fuchs, Printed in Germany
2
2
4
2
4
2
10
2
3
3
2
3
2

Hide quick links: