Pepperl+Fuchs VBG-PB-K25 Manual page 88

As-i/profibus gateway in acc. to specification 3.0
Table of Contents

Advertisement

4. Write permanent parameter (power on parameter) to master
Example as above:16-bit module at address 4 with PP = 07
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
...
Byte 12 00
Byte 1
Byte 2
...
Byte 12 00
No result because toggle bit = 0
Setting the toggle bit:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
...
Byte 12 00
Byte 1
Byte 2
Byte 3
...
Byte 12 00
The permanent parameter for the 16-bit module is written.
This command must be repeated for all 31 A-slaves and all 31 B-slaves. If you
don't connect a slave to an address, write the default value to the master (F
a permanent parameter.
Subject to reasonable modifications due to technical advances.
86
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Request: SET_PP
43
(SET_PP)
hex
00
(T = 0, master 1, single master)
hex
04
(slave address to write to master)
hex
07
(PP to write (use low nibble))
hex
00
(LDS byte 1)
hex
...
hex
Response
00
(or old values)
hex
00
(or old values)
hex
...
(or old values)
hex
Request: SET_PP
43
(SET_PP)
hex
80
(T = 0, master 1, single master)
hex
04
(slave address to write to master)
hex
07
(PP to write (use low nibble)
hex
00
hex
...
hex
Response
43
hex
80
(T = 1, Result = 0)
hex
00
hex
...
hex
AS-Interface
Command Interface
hex
hex
Copyright Pepperl+Fuchs, Printed in Germany