Ec-Flags And As-I Watchdog - Pepperl+Fuchs VBG-PB-K25 Manual

As-i/profibus gateway in acc. to specification 3.0
Table of Contents

Advertisement

input data
F0 ConfigError
F1 APF
F2 PeripheryFault
F3 ConfigurationActive
ConfigError:
APF:
PeripheryFault:
ConfigurationActive: 0 = ConfigurationActive, 1 = ConfigurationInactive
Offline:
LOS-Master-Bit
A rising edge of F2 and F3 switch the master to the desired mode.
A rising edge of the "LOS master bit" effects that all bits in the LOS are set. A falling
edge effects that all bits are deleted.
7.1.3.2

EC-Flags and AS-i watchdog

In addition to EC flags, the AS-i watchdog flags will be transferred in dignostic data
too.
Diagnostic data are assembled as follows:
ec-flags (high):
Bit 0:
Bit 1 ... Bit 2 reserved
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
ec-flags (low):
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Flags
output data
Offline
LOS master bit
→ ConfigurationMode
→ ProtectedMode
0 = ConfigOK, 1 = ConfigError
0 = AS-i Power OK, 1 = AS-i Power Fail
0 = PeripheryOK, 1 = PeripheryFault
0 = Online, 1 = Offline
0 = Offline by ConfigError deactivated
1 = Offline by ConfigError activated
periphery fault
failure redundant 24 V (option single master)
earth fault
over voltage
noise
duplicate address
configuration error
slave with address0 detected
Auto_address_assignment not possible
Auto_address_assingment available
configuration mode actice
not in normal operation
AS-i/PROFIBUS Gateway
PROFIBUS DP
Copyright Pepperl+Fuchs, Printed in Germany
25