8.3.3
Store new Configuration for all Slaves
1. Switch master in configuration mode
2. Write slave configuration to master
3. Write new list of projected slaves (LPS)
4. Write permanent parameter (PP) to master
5. Switch master to protected mode
6. Wait until master is in normal operation Mode (and protected mode)
12 Byte Management
1. Set master in config mode
Byte 1
Byte 2
Byte 3
Byte 4
...
Byte 12 00
Byte 1
Byte 2
Byte 3
Byte 4
...
Byte 12 00
No result because toggle bit = 0.
Set the toggle bit:
Byte 1
Byte 2
Byte 3
Byte 4
...
Byte 12 00
Subject to reasonable modifications due to technical advances.
82
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Request: SET_OP_MODE
0C
(SET_OP_MODE)
hex
00
(T = 0, master 1, single master)
hex
01
(= config mode)
hex
00
hex
...
hex
Response
00
(or old values)
hex
00
(or old values)
hex
00
(or old values)
hex
00
(or old values)
hex
...
(or old values)
hex
Request: SET_OP_MODE
0C
(SET_OP_MODE)
hex
80
(T = 1, master 1, single master)
hex
01
(= config mode)
hex
00
hex
...
hex
AS-Interface
Command Interface
Copyright Pepperl+Fuchs, Printed in Germany