Bus Termination - Pepperl+Fuchs VBG-PB-K25 Manual

As-i/profibus gateway in acc. to specification 3.0
Table of Contents

Advertisement

5.2.1

Bus Termination

If the AS-i/PROFIBUS gateway is at the end of the PROFIBUS line, the termination
resistors in the PROFIBUS connector have to be switched on.
PIN
Designation of the SUB-D connector
Pin 3 Data line B („RxD/TxD-P")
Pin 5 DGND (0 V)
Pin 6 VP / +5 V
Pin 8 Data line A („RxD/TxD-N")
If the gateway will be installed in a two wire circuit (only A + B Line), means no
5 Volt supply, the gateway has to be placed at the end of the line.
Please install the bustermination as close as possible to the Sub-D connector
of the gateway.
Terminating resistors with RS 485:
5V
390
220
390
GND
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Connections, Displays and Operating Keys
A
A
B
B
Host
AS-i Master
AS-i/PROFIBUS Gateway
5V
390
A
220
B
390
GND
AS-i Master
Copyright Pepperl+Fuchs, Printed in Germany
11

Hide quick links:

Advertisement

Table of Contents
loading