Service
8
Fault/error table
Subfault: 16.25
Description: User-defined current limit too low for standstill current
Response: Output stage inhibit
User-defined current limit value too small for min-
imum standstill current.
Subfault: 16.26
Description: Nominal values incomplete or implausible
Response: Output stage inhibit
During startup using nameplate data: Nominal
voltage, nominal current, nominal speed or nom-
inal torque are not entered or are not plausible.
Subfault: 16.27
Description: Maximum current or maximum torque not plausible
Response: Output stage inhibit
During startup using nameplate data: Maximum
current or maximum torque not entered, or maxi-
mum current and maximum torque not plausible.
Subfault: 16.30
Description: Faulty EtherCAT
Response: Warning
Faulty EtherCAT
tion status.
EEPROM not loaded; binary file not loaded.
Faulty EEPROM loading procedure.
Faulty EEPROM checksum.
Subfault: 16.40
Description: Data of selected motor not valid
Response: Output stage inhibit
Startup data set on replaceable memory module
not valid for this motor.
220
Operating Instructions – MOVIMOT
Cause
Cause
Cause
®
EEPROM configuration state
Cause
®
PLUS
/SBus
EEPROM configura-
Cause
®
flexible
Measure
Increase the user-defined current limit, or disable
the standstill current function.
Measure
Enter or check nominal voltage, nominal current,
nominal speed, and nominal torque.
Measure
Check the maximum current and maximum
torque.
Measure
Contact the SEW‑EURODRIVE Service.
Contact the SEW‑EURODRIVE Service.
Contact the SEW‑EURODRIVE Service.
Measure
Replace the memory module.