F432

Speed Limit (torque=0) Band

Program ⇒ Torque ⇒ Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets a plus-or-minus value (range) for the Speed Limit Torque Level
(F431).
Rotation in Specified Direction ONLY
Program ⇒ Torque ⇒ Torque Speed Limiting
This parameter Enables/Disables the Forward Run or Reverse Run mode.
If either direction is disabled, commands received for the disabled direction will
not be recognized.
If both directions are disabled, the received direction command will determine
the direction of the motor rotation.
Settings
0 — Disabled
1 — Enabled

Power Running Torque Limit 1

Program ⇒ Torque ⇒ Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If Setting is selected, the value set at
Torque Limit #1 input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F441
(setting)

Power Running Torque Limit 1 Level

Program ⇒ Torque ⇒ Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit #1
setting if
F441
is selected at parameter F440.
This value provides the positive torque upper limit for the #1 motor.
H9 ASD Installation and Operation Manual
F441
is used as the Power Running
Direct Access Number — F432
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F435
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F440
Parameter Type — Selection List
Factory Default
—F441
Setting
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
F441
157