F214

RR Input Point 1 Rate

Program ⇒ Torque ⇒ Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the RR input terminal:
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode
⇒ RR.
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode
Selection ⇒ Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control
from the RR input terminal:
• Set RR Input Point 1 Rate (F214).
• Set RR Input Point 1 Setting (F210) — the input analog signal level that
corresponds to the torque setting at RR Input Point 1 Rate.
• Set RR Input Point 2 Rate (F215).
• Set RR Input Point 2 Setting (F212) — the input analog signal level that
corresponds to the frequency setting at RR Input Point 2 Rate.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
Once set, as the RR input voltage changes, the output torque of the ASD will
vary in accordance with the above settings.
This parameter sets RR Input Point 1 Rate and is the output torque value that
is associated with the setting of RR Input Point 1 Setting when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.

RR Input Point 2 Rate

Program ⇒ Torque ⇒ Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output
pattern for a given RR input level.
This parameter sets RR Input Point 2 Rate and is the output torque value that
is associated with the setting of RR Input Point 2 Setting when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See RR Input Point 1 Rate for more information on this setting.
112
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
Direct Access Number — F215
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
H9 ASD Installation and Operation Manual