Regenerative Braking Torque Limit; Regenerative Braking Torque Limit 1 Level; Power Running Torque Limit 2 Level; Regenerative Braking Torque Limit 2 Level - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F442

Regenerative Braking Torque Limit 1

Program ⇒ Torque ⇒ Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(setting)

Regenerative Braking Torque Limit 1 Level

Program ⇒ Torque ⇒ Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque Limit
#1 if
F443
is selected at parameter F442.
Set this parameter to 250% to disable this function.

Power Running Torque Limit 2 Level

Program ⇒ Torque ⇒ Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Regenerative Braking Torque Limit 2 Level

Program ⇒ Torque ⇒ Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Power Running Torque Limit 3 Level

Program ⇒ Torque ⇒ Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
158
F443
is used for this parameter.
Direct Access Number — F442
Parameter Type — Selection List
Factory Default —
F443
Setting
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F445
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F446
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
H9 ASD Installation and Operation Manual
F446