F701
Display Units for Voltage and Current
Program ⇒ Utilities ⇒ Display Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Display Unit Multiplication Factor
Program ⇒ Utilities ⇒ Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
front panel display of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example: An output frequency of 100 Hz would be displayed as 50 Hz if
using a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters are not affected by this
setting (i.e., F364, F365, F367, and F368).
Display Unit Selection
Program ⇒ Utilities ⇒ Display Parameters
This parameter is used in conjunction with
frequency is displayed on the front panel.
The multiplier setting of
F702
All Frequencies are selected at this parameter.
The multiplier setting of
F702
and
F368
ONLY if PID Process Data is selected at this parameter.
Settings:
0 — All Frequencies
1 — PID Process Data
Display Gradient Characteristic
Program ⇒ Utilities ⇒ Display Parameters
The ASD-displayed response to output speed changes will be displayed as
directly proportional or inversely proportional as a function of this parameter
setting.
Selecting Negative Gradient displays an increased output speed as going more
negative.
Selecting Positive Gradient displays an increased output speed as going more
positive.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
H9 ASD Installation and Operation Manual
F702
to set the method in which the
will be applied to the display of all frequencies if
will be applied to parameters F364, F365, F367,
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00 (OFF)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Direct Access Number — F703
Parameter Type — Selection List
Factory Default — All Frequencies
Changeable During Run — Yes
Direct Access Number — F705
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
F705
199