Acceleration Suspend Frequency; Acceleration Suspend Time; Deceleration Suspend Frequency; Deceleration Suspend Time - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F350

Acceleration Suspend Frequency

Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
When Enabled at F349, this parameter is used to set the frequency at which the
Acceleration Suspend function will activate.
During acceleration, this parameter sets the frequency at which acceleration
will stop and the motor will run at the setting of this parameter for the time
setting of F351.

Acceleration Suspend Time

Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
When Enabled at F349, this parameter is used to set the duration of activation
of the Acceleration Suspend function when initiated by reaching the
Acceleration Suspend Frequency setting (F350).
Once this parameter times out the acceleration rate will resume from the point
of suspension.

Deceleration Suspend Frequency

Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
When Enabled at F349, this parameter is used to set the frequency at which the
Deceleration Suspend function will activate.
During deceleration, this parameter sets the frequency at which deceleration
will stop and the motor will run at the setting of this parameter for the time
setting of
F353.

Deceleration Suspend Time

Program ⇒ Fundamental ⇒ Accel/Decel #1 Settings
When Enabled at F349, this parameter is used to set the duration of activation
of the Deceleration Suspend function when initiated by reaching the
Deceleration Suspend Frequency setting (F352).
Once this parameter times out the deceleration rate will resume from the point
of suspension.
H9 ASD Installation and Operation Manual
Direct Access Number — F350
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F351
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
Direct Access Number — F352
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F353
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
F353
145