F206

V/I Input Point 2 Rate

Program ⇒ Torque ⇒ Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
This parameter sets V/I Input Point 2 Rate and is the output torque value that
is associated with the setting of V/I Input Point 2 Setting when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Input Point 1 Rate for more information on this setting.
Frequency Mode 2
Program ⇒ Fundamental ⇒ Standard Mode Selection
This parameter is used to set the source of the frequency command signal to be
used as Frequency Mode 2 in the event that Frequency Mode 1 is disabled or
if Frequency Mode 2 is set up as the primary control parameter. See
F200
for additional information on this setting.
Settings:
1 — V/I
2 — RR
3 — RX
4 — Not Used
5 — EOI Keypad
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (terminal board)
11 — Pulse Input (option)
12 — Pulse Input (motor CPU)
13 — Binary/BCD Input (option)

Frequency Mode Priority Switching Frequency

Program ⇒ Fundamental ⇒ Standard Mode Selection
This parameter establishes a threshold frequency that will be used as a reference
when determining when to switch the output frequency control source from the
Frequency Mode 1 setting to the Frequency Mode 2 setting.
See
F200
for additional information on this setting.
108
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number — F207
Parameter Type — Selection List
Factory Default — V/I
Changeable During Run — Yes
F004
and
Direct Access Number — F208
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.10
Maximum — Max. Freq. (F011)
Units — Hz
H9 ASD Installation and Operation Manual
F208