Toshiba H9 Installation And Operation Manual page 225

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F906
Input Function Target 1
Program ⇒ My Function ⇒ My Function Unit 2
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 1
terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
241, or
Table 10 on pg.
See
F977
for more information on this parameter.
Input Function Command 1
Program ⇒ My Function ⇒ My Function Unit 2
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 11 on pg. 245
lists the available selections. Their use and selection
requirements are described in an example at F977.
Input Function Target 2
Program ⇒ My Function ⇒ My Function Unit 2
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 2
terminal.
This setting assigns the function of the programmable Input Function Target 2
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
241, or
Table 10 on pg.
See
F977
for more information on this parameter.
Input Function Command 2
Program ⇒ My Function ⇒ My Function Unit 2
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 11 on pg. 245
lists the available selections. Their use and selection
requirements are described in an example at F977.
Input Function Target 3
Program ⇒ My Function ⇒ My Function Unit 2
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 3
terminal.
This setting assigns the function of the programmable Input Function Target 3
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
241, or
Table 10 on pg.
See
F977
for more information on this parameter.
H9 ASD Installation and Operation Manual
Table 7 on pg.
243.
Table 7 on pg.
243.
Table 7 on pg.
243.
Direct Access Number — F906
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
240,
Direct Access Number — F907
Parameter Type — Selection List
Factory Default — 0 (NOP)
Direct Access Number — F908
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
240,
Direct Access Number — F909
Parameter Type — Selection List
Factory Default — 0 (NOP)
Direct Access Number — F910
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
240,
F910
217

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents