F424

Load Sharing Gain Input

Program ⇒ Torque ⇒ Torque Control
This parameter Enables/Disables the Load Sharing Gain input function.
This feature is enabled by selecting a Load Sharing Gain input signal source.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-wire
6 — RS485 4-wire
7 — Communication Option Board
8 — RX2 Option (AI1)

Forward Speed Limit Input

Program ⇒ Torque ⇒ Torque Speed Limiting
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the input selected here.
If Setting is selected, the value set at
Limit input.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —
F426
(setting)
Forward Speed Limit Level
Program ⇒ Torque ⇒ Torque Control
This parameter provides a value to be used as the Forward Speed Limit setting
if
F426
is selected at F425.
H9 ASD Installation and Operation Manual
F426
is used as the Forward Speed
Direct Access Number — F424
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F426
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
F426
155