Short Circuit Protection Recommendations - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

Short Circuit Protection Recommendations

Table 22. 230/240 and 400/480-Volt ASD recommended circuit breaker selection.
Model Number
VT130H9U
2035
2055
2080
2110
2160
2220
2270
2330
2400
2500
2600
2750
210K
212K
4055
4080
4110
4160
4220
4270
4330
4400
4500
4600
4750
410K
412K
415K
420K
425K
430K
435K
440K
H9 ASD Installation and Operation Manual
Continuous Output Current
HP
(Amps)
3.0
10.0
5.0
17.5
7.5
27.5
10
33.0
15
54.0
20
66.0
25
76.0
30
90.0
40
120
50
152
60
176
75
221
100
285
125
365
5
10.5
7.5
14.3
10
17.6
15
27.7
20
33.0
25
41.0
30
48.0
40
66.0
50
79.0
60
94.0
75
116
100
160
125
179
150
215
200
259
250
314
300
387
350
434
400
495
Circuit Breaker Part Number
HLL36025
HLL36025
HLL36040
HLL36050
HLL36070
HLL36090
HLL36100
HLL36100
HLL36125
HLL36150
JLL36200
Contact Toshiba Customer Service
HLL36025
HLL36040
HLL36050
HLL36070
HLL36090
HLL36100
HLL36100
HLL36125
HLL36150
JLL36200
JLL36225
JLL36250
LIL36300
LIL36300
LIL36400
LIL36400
Contact Toshiba Customer Service