F955
Input Function Target 2
Program ⇒ My Function ⇒ My Function Unit 7
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 2
terminal.
This setting assigns the function of the programmable Input Function Target 2
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
241, or
Table 10 on pg.
See
F977
for more information on this parameter.
Input Function Command 2
Program ⇒ My Function ⇒ My Function Unit 7
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 11 on pg. 245
lists the available selections. Their use and selection
requirements are described in an example at F977.
Input Function Target 3
Program ⇒ My Function ⇒ My Function Unit 7
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 3
terminal.
This setting assigns the function of the programmable Input Function Target 3
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
241, or
Table 10 on pg.
See
F977
for more information on this parameter.
Output Function Assigned
Program ⇒ My Function ⇒ My Function Unit 7
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the Output Function Assigned terminal.
This setting assigns the function of the programmable Output Function
Assigned data location to one of the functions listed in the Input Setting field
of
Table 8 on pg.
241.
Settings:
0 – 3099
See the My Function Instruction Manual (P/N 58692) and
information on this parameter.
H9 ASD Installation and Operation Manual
Table 7 on pg.
243.
Table 7 on pg.
243.
F977
for more
Direct Access Number — F955
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
240,
Direct Access Number — F956
Parameter Type — Selection List
Factory Default — 0 (NOP)
Direct Access Number — F957
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
240,
Direct Access Number — F958
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
F958
227