F216

RX Input Point 1 Setting

Program ⇒ Frequency ⇒ Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RX input level that is associated with RX Input Point 1
Frequency when operating in the Speed Control mode or is associated with
the RX Input Point 1 Rate when operating in the Torque Control mode.
RX Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the RX input terminal:
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode
1 ⇒ RX.
• Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode
Selection ⇒ Terminal Block.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RX input terminal:
• Set RX Input Point 1 Frequency (F217).
• Set RX Input Point 1 Setting (F216) — the input analog signal level that
corresponds to the speed setting at RX Input Point 1 Frequency.
• Set RX Input Point 2 Frequency (F219).
• Set RX Input Point 2 Setting (F218) — the input analog signal level that
corresponds to the speed setting at RX Input Point 2 Frequency.
• Provide a Run command (F and/or R).
Once set, as the RX input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the RX input signal
range.
See parameter
F474
and
F475
response.

RX Input Point 1 Frequency

Program ⇒ Frequency ⇒ Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RX Input Point 1 Frequency and is the frequency that is
associated with the setting of RX Input Point 1 Setting when operating in the
Speed Control mode.
See RX Input Point 1 Setting for more information on this setting.
H9 ASD Installation and Operation Manual
for information on fine-tuning this terminal
Direct Access Number — F216
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Frequency Settings
Direct Access Number — F217
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F217
113