Toshiba H9 Installation And Operation Manual page 50

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

EOI Command Mode
The EOI Command mode is accessed by pressing the ESC key from the Frequency Command screen.
The control settings of the EOI Command menu are effective for EOI control only.
The EOI Command mode provides quick access to the following menu parameters:
Direction — Forward or Reverse.
Stop Pattern — The Decel Stop or Coast Stop settings determines the method used to stop the
motor when using the Stop|Reset key of the EOI. The Decel Stop setting enables the Dynamic
Braking system setup at
The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note:
The Stop Pattern setting has no effect on the Emergency Off settings of F603.
V/f Group — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user
settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Electronic
Thermal Protection. Expanded descriptions of these parameters may be found in the section titled
Direct Access Parameter Information on pg.
Accel/Decel Group — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/
Decel profiles is comprised of 3 user settings: Acceleration, Deceleration, and Pattern. Expanded
descriptions of these parameters may be found in the section titled
Information on pg. 76
Feedback in Panel Mode — This feature enables or disables the PID feedback function.
Torque Limit Group — This parameter is used to select 1 of 4 preset positive torque limits to apply
to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at
F441, F444, F446, and F448, respectively.
42
F304
or the DC Injection Braking system setup at F250, F251, and F252.
76.
(or see F009).
Direct Access Parameter
H9 ASD Installation and Operation Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents